Title: Amending Title 4 of The Philadelphia Code, entitled "The Philadelphia Building Construction and Occupancy Code," by amending Subcode "M" (The Philadelphia Mechanical Code) and adopting the 2021 edition of the "International Mechanical Code," as published by the International Code Council, with amendments thereto, as authorized by the Pennsylvania Uniform Construction Code Act, all under certain terms and conditions.
Sponsors: Council President Johnson, Councilmember Driscoll
Code sections: Title 4 - THE PHILADELPHIA BUILDING CONSTRUCTION AND OCCUPANCY CODE
Attachments: 1. Bill No. 26039100

Title

Amending Title 4 of The Philadelphia Code, entitled “The Philadelphia Building Construction and Occupancy Code,” by amending Subcode “M” (The Philadelphia Mechanical Code) and adopting the 2021 edition of the “International Mechanical Code,” as published by the International Code Council, with amendments thereto, as authorized by the Pennsylvania Uniform Construction Code Act, all under certain terms and conditions.

 

Body

THE COUNCIL OF THE CITY OF PHILADELPHIA HEREBY ORDAINS:

 

SECTION 1. The contents of Subcode “M” of Title 4 of The Philadelphia Code, entitled “The Philadelphia Mechanical Code,” are hereby deleted and replaced with the following:

SUBCODE "M" (THE PHILADELPHIA MECHANICAL CODE)

 

Article M-1.0 Adoption of the "2021 International Mechanical Code," pursuant to the Pennsylvania Uniform Construction Code Act (“Act”), with state amendments and local amendments that were in effect prior to enactment of the Act or approved pursuant to Section 503 of the Act.

 

§ M-1.1 The "2021 International Mechanical Code," as published by the International Code Council, is hereby adopted as the Mechanical Code of the City of Philadelphia and is incorporated as if fully set forth herein, subject to the amendments provided in this Subcode M.

 

§ M-1.1.1 The numbers of all local amendments shall be preceded with the prefix "M-".

 

§ M-1.1.2 Throughout the code, references to "International" codes or "ICC" codes shall                      be deemed to refer to the "Philadelphia" codes of the same name.

 

*                     *                     *

 

CHAPTER 1
SCOPE AND ADMINISTRATION

 

[Delete contents of entire Chapter and replace as follows:]

SECTION M-101 GENERAL

M-101.1 Title. These provisions shall be known as the Philadelphia Amendments to the International Mechanical Code, and will be referred to herein as the "Philadelphia Mechanical Code" or "this code".

M-101.2 Scope. The Philadelphia Mechanical Code shall regulate the design, installation, maintenance, alteration and inspection of mechanical systems that are permanently installed and utilized to provide control of environmental conditions and related processes within buildings. This code shall also regulate those mechanical systems, system components, equipment and appliances specifically addressed herein. The installation of fuel gas distribution piping and equipment, fuel gas-fired appliances and fuel gas-fired appliance venting systems shall be regulated by the Philadelphia Fuel Gas Code (Subcode G).

Exception: Detached one- and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories high with separate means of egress and their accessory structures shall comply with the Philadelphia Residential Code (Subcode R).

M-101.3 Appendices. No appendices are adopted as a part of this code.

M-101.4 Intent. The purpose of this code is to provide minimum standards to safeguard life or limb, health, property and public welfare by regulating and controlling the design, construction, installation, quality of materials, location, operation and maintenance or use of mechanical systems.

M-101.5 Administrative provisions. This Chapter contains those provisions that are unique to the administration of this code. All other administrative provisions applicable to this code are as set forth in the Administrative Code.

M-101.6 Conflicts. Pursuant to the Pennsylvania Uniform Construction Code Act, a provision of the "'International Mechanical Code" does not apply if the provision conflicts with the Boiler and Unfired Pressure Vessel Law (35 P. S. §§ 1331.1 - 1331.9).

 

SECTION M-102 INSPECTIONS AND TESTING

M-102.1 Evaluation and follow-up inspection services. Prior to the approval of a prefabricated construction assembly having concealed work and the issuance of a permit, the code official shall require the submittal of an evaluation report from an approved agency on each prefabricated construction assembly. The report shall indicate the complete details of the mechanical system, including a description of the system and its components, the basis upon which the system is being evaluated, test results and similar information and other data as necessary for the code official to determine conformance to this code.

Exception: Manufactured and Industrialized housing pursuant to Section A-102.12 of the Administrative Code.

M-102.1.1 Follow-up inspection. Except where ready access is provided to mechanical systems, service equipment and accessories for complete inspection at the site without disassembly or dismantling, the code official shall conduct in-plant inspections to ensure conformance to the approved evaluation report or shall accept inspection reports from an approved independent inspection agency. The inspection agency shall furnish the code official with the follow-up inspection manual and a report of inspections upon request. The mechanical system shall have an identifying label permanently affixed to the system indicating that factory inspections have been performed.

M-102.1.2 Test and inspection records. Required test and inspection records shall be available to the code official at all times during the fabrication of the mechanical system and the erection of the building; or such records as the code official designates shall be filed.

M-102.2 Testing. Mechanical systems shall be tested as required in this code and in accordance with Sections M-102.2.1 through M-102.2.3. Tests shall be made by the permit holder after notifying the code official, who shall have the authority to observe the tests.

M-102.2.1 New, altered, extended or repaired systems. New mechanical systems and parts of existing systems, which have been altered, extended, renovated or repaired, shall be tested as prescribed herein to disclose leaks and defects.

M-102.2.2 Apparatus, instruments, material and labor for tests. Apparatus, instruments, material and labor required for testing a mechanical system or part thereof shall be furnished by the permit holder.

M-102.2.3 Reinspection and testing. Where any work or mechanical system does not pass an initial test or inspection, the necessary corrections shall be made so as to achieve compliance with this code. The work or system shall then be reinspected or re-tested and the results resubmitted to the code official as appropriate.

 

*                     *                     *

 

CHAPTER 3

GENERAL REGULATIONS

 

*                     *                     *

 

SECTION 307 CONDENSATE DISPOSAL

 

*                     *                     *

[Delete Section 307.2.1.1, and replace as follows:]

M-307.2.1.1 Disposal into Clothes Washer Box. Condensate shall be permitted to discharge into a clothes washer box with dual drainage outlets with one outlet dedicated to the clothes washer discharge and one outlet dedicated to condensate discharge. Condensate shall also be permitted to discharge into a clothes washer box with a single drainage outlet where the inlet of the clothes washer box outlet is sized to accommodate both the clothes washer discharge and the condensate discharge.

 

*                     *                     *

 

CHAPTER 11

REFRIGERATION

 

*                     *                     *

 

SECTION 1101 GENERAL

 

*                     *                     *

 

[Add Section 1101.2.1 as follows:]

M-1101.2.1 Group A2L, A2, A3, and B1 high-probability equipment.  High-probability equipment using Group A2L, A2, A3, or B1 refrigerant shall comply with UL 484, UL/CSA 60335-2-40, or UL/CSA 60335-2-89.

 

*                     *                     *

 

SECTION 1103 REFRIGERATION SYSTEM CLASSIFICATION

 

*                     *                     *

 

[Delete Table 1103.1 and replace as follows:]

TABLE M-1103.1 REFRIGERANT CLASSIFICATION, AMOUNT, AND OEL

 

 

Chemical  Refrigerant

Formula

Chemical Name of Blend

Refrigerant Safety Group Classification

Amount of Refrigerant Per Occupied Space

[F] Degrees of Hazarda

 

 

 

 

RCL

LFLf

OELd

 

 

 

 

 

Pounds      per            1000       cubic  feet

ppm

g/m3

Pounds      per            1000       cubic feet

ppm

g/m3

ppm

 

R-11 c

CCI3F

trichlorofluoromethane

A1

0.39

1,100

 6.1

-

-

-

1000

2-0-0b

R-12 c

CCI2F2

dichlorodifluoromethane

A1

5.6

18,000

90

-

-

-

1000

2-0-0b

R-13 c

CCIF3

chlorotrifluoromethane

A1

-

-

-

-

-

-

1000

2-0-0b

R-13B1 c

CBrF3

bromotrifluoromethane

A1

-

-

-

-

-

-

1000

2-0-0b

* * *

R-32

CH2F2

difluoromethane (methylene fluoride)

 A2L

0.8

36,000

77

19.1

144,000

306

1,000

1-4-0

* * *

R-50

CH4

methane

A3

-

-

-

-

50,000

-

1000

-

R-113 c

CCI2FCCIF2

1,1,2-trichloro-1,2,2-trifluoroethane

A1

1.2

2,600

20

-

-

-

1000

2-0-0b

R-114 c

CCIF2CCIF2

1,2-dichloro-1,1,2,2-tetrafluoroethane

A1

8.7

20,000

140

-

-

-

1000

2-0-0b

* * *

R-141b

CH3CCI2F

1,1,-dichloro-1-difluororethane

-

0.78

2,600

12

17.8

60,000

287

500

2-1-0

R-142b

CH3CCIF2

1-chloro-1,1-difluoroethane

A2

5.1

20,000

 82

20.4

80,000

329

1,000

2-4-0

R-143a

CH3CF3

1,1,1-trifluoroethane

 A2L

 4.4

21,000

70

17.5

82,000

282

1,000

2-0-0b

R-152a

CH3CHF2

1,1-difluoroethane

A2

2.0

12,000

32

8.1

48,000

130

1,000

1-4-0

R-170

CH3CH3

ethane

A3

0.54

7,000

 8.6

2.4

31,000

38

1,000

2-4-0

R-E170

CH3OCH3

Methoxymethane (dimethyl ether)

A3

1.0

8,500

16

4

34,000

64

1,000

-

* * *

R-290

CH3CH2CH3

propane

A3

0.59

5,300

9.5

2.4

21,000

38

1,000

2-4-0

R-C318

(CF2)4

octafluorocyclobutane

A1

41

80,000

 650

-

-

-

1,000

-

R-400c

zeotrope

R-12/114 (50.0/50.0)

A1

10

28,000

160

-

-

-

1,000

2-0-0b

R-400c

zeotrope

R-12/114 (60.0/40.0)

A1

11

30,000

170

-

-

-

1,000

-

* * *

R-403B

zeotrope

R-290/22/218 (5.0/56.0/39.0)

A1

18

68,000

290

-

-

-

1,000

2-0-0b

* * *

R-406A

zeotrope

R-22/600a/142b (55.0/4.0/41.0)

A2

4.7

21,000

75

18.8

82,000

301.9

1,000

-

* * *

R-408A

zeotrope

R-125/143a/22 (7.0/46.0/47.0)

A1

21

94,000

 330

-

-

-

1,000

2-0-0b

* * *

R-411A

zeotrope

R-127/22/152a (1.5/87.5/11.0)

A2

2.9

14,000

46

11.6f

55,000f

185.6f

 970

-

R-411B

zeotrope

R-1270/22/152a (3.0/94.0/3.0)

A2

2.8

13,000

45

14.8f

70,000f

283.3f

 940

-

R-412A

zeotrope

R-22/218/142b (70.0/5.0/25.0)

A2

5.1

22,000

82

20.5f

87,000f

328.6f

1,000

-

R-413A

zeotrope

R-218/134a/600a (9.0/88.0/3.0)

A2

5.8

22,000

93

23.4f

88,000f

376.9f

1,000

-

* * *

R-415A

zeotrope

 R-22/152a (82.0/18.0)

A2

2.9

14,000

47

11.7g

56,000g

187.9g

1,000

-

R-415B

zeotrope

R-22/152a (25.0/75.0)

A2

2.1

12,000

34

8.4

47,000

135.1

1,000

-

* * *

R-417A

zeotrope

R-125/134a/600 (46.6/50.0/3.4)

A1

3.5

13,000

 55

-

-

-

1,000

2-0-0b

R-417B

zeotrope

R-125/134a/600 (79.0/18.3/2.7)

A1

4.3

15,000

 69

-

-

-

1,000

-

R-418A

zeotrope

R-290/22/152a (1.5/96.0/2.5)

A2

4.8

22,000

77

19.2g

89,000g

308.4g

1,000

-

R-419A

zeotrope

R-125/134a/E170 (77.0/19.0/4.0)

A2

4.2

15,000

67

16.7g

60,000g

268.6g

1,000

-

R-419B

zeotrope

R-125/134a/E170 (48.5/48.0/3.5)

A2

4.6

17,000

74

18.5g

69,000g

297.3g

1,000

-

R-420A

zeotrope

R-134a/142b (88.0/12.0)

A1

12

44,000

 180

-

-

-

1,000

2-0-0b

* * *

R-423A

zeotrope

R-134a/227ea (52.5/47.5)

A1

19

59,000

 300

-

-

-

1,000

2-0-0b

* * *

R-429A

zeotrope

R-E170/152a/600a (60.0/10.0/30.0)

A3

0.81

6,300

13

3.2

25,000

83.8

1,000

-

R-430A

zeotrope

R-152a/600a (76.0/24.0)

A3

1.3

8,000

21

5.2

32,000

44

1,000

-

R-431A

zeotrope

R-290/152a (71.0/29.0)

A3

 0.68

5,500

11

2.7

22,000

38.6

1,000

-

R-432A

zeotrope

R-1270/E170 (80.0/20.0)

A3

0.13

1,200

2.1

2.4

22,000

39.2

 550

-

R-433A

zeotrope

R-1270/290 (30.0/70.0)

A3

0.34

3,100

5.5

2.4

20,000

32.4

 760

-

R-433B

zeotrope

R-1270/290 (5.0-95.0)

A3

 0.39

3500

 6.3

2.0

18,000

32.1

950

-

R-433C

zeotrope

R-1270/290 (25.0-75.0)

A3

0.41

3,600

 6.5

2.0

18,000

83.8

790

-

* * *

R-435A

zeotrope

R-E170/152a (80.0/20.0)

A3

1.1

8,500

17

4.3

34,000

68.2

1,000

-

R-436A

zeotrope

R-290/600a (56.0/44.0)

A3

0.5

4,000

8.1

2.0

16,000

32.3

1,000

-

R-436B

zeotrope

R-290/600a (52.0/48.0)

A3

0.51

4,000

8.1

2.0

16,000

32.7

1,000

-

* * *

R-439A

zeotrope

R-32/125/600a (50.0/47.0/3.0)

A2

4.7

26,000

76

18.9

104,000

303.3

990

-

R-440A

zeotrope

R-290/134a/152a (0.6/1.6/97.8)

A2

1.9

12,000

31

7.8h

46000h

124.7h

1,000

-

R-441A

zeotrope

R-170/290/600a/600 (3.1/54.8/6.0/36.1)

A3

0.39

3,200

6.3

2.0

16,000

31.7

1,000

-

* * *

R-443A

zeotrope

R-1270/290/600a (55.0/40.0/5.0)

A3

0.19

1,700

3.1

2.2

20,000

35.6

580

-

R-444A

zeotrope

R-32/152a/1234ze(E) (12.0/5.0/83.0)

 A2L

 5.0

21,000

 80

19.9

82,000

319.4

850

-

R-444B

zeotrope

R-32/152a/1234ze(E) (41.5/10.0/48.5)

 A2L

4.3

23,000

69

17.3

93,000

277.3

890

-

R-445A

zeotrope

R-744/134a/1234ze(E) (6.0/9.0/85.0)

 A2L

4.2

16,000

67

2.7

63,000

347.4

930

-

R-446A

zeotrope

R-32/1234ze(E)/600 (68.0/29.0/3.0)

 A2L

2.5

16,000

39

13.5

62,000

217.4

930

-

R-447A

zeotrope

R-32/125/1234ze(E) (68.0/3.5/28.5)

 A2L

2.6

16,000

42

18.9

65,000

303.5

900

-

R-447B

zeotrope

R-32/125/1234ze(E) (68.0/8.0/24.0)

 A2L

 2.6

16,000

 42

 19.5

121,000

312.7

970

-

* * *

R-451A

zeotrope

R-1234yf/134a (89.8/10.2)

 A2L

 5.0

18,000

81

20.3

70,000

326.6

520

-

R-451B

zeotrope

R-1234yf/134a (88.8/11.2)

 A2L

 5.0

18,000

81

20.3

70,000

326.6

530

-

* * *

R-452B

zeotrope

R-32/125/1234yf (67.0/7.0/26.0)

 A2L

 4.8

30,000

 77

19.3

119,000

310.5

780

-

* * *

R-454A

zeotrope

R-32/1234yf (35.0/65.0)

 A2L

 3.2

16,000

 52

18.3

63,000

293.9

690

-

R-454B

zeotrope

R-32/1234yf (68.9/31.1)

 A2L

 3.1

19,000

 49

22

77,000

352.6

850

-

R-454C

zeotrope

R-32/1234yf (21.5/78.5)

 A2L

 4.4

19,000

 71

18

62,000

289.5

620

-

R-455A

zeotrope

R-744/32/1234yf (3.0/21.5/75.5)

 A2L

 4.9

22,000

 79

26.9

118,000

432.1

650

-

* * *

R-457A

zeotrope

R-32/1234yf/152a (18.0/70.0/12.0)

 A2L

 3.4

15,000

 54

13.5

60,000

216.3

650

-

* * *

R-459A

zeotrope

R-32/1234yf/1234ze(E) (68.0/26.0/6.0)

 A2L

 4.3

27,000

 69

17.4

107,000

278.7

870

-

R-459B

zeotrope

R-32/1234yf/1234ze(E) (21.0/69.0/10.0)

 A2L

 5.8

16,000

 92

23.3

99,000

373.5

640

-

* * *

R-462A

zeotrope

R-32/125/143a/134a/600 (9.0/42.0/2.0/44.0/3.0)

A2

3.9

16,000

62

16.6f

105000f

265.8f

1,000

-

* * *

R-500c

zeotrope

R-12/152a (73.8/26.2)

A1

 7.4

29,000

120

-

-

-

1,000

2-0-0b

R-501c

zeotrope

R-22/12 (75.0/25.0)

A1

13

54,000

210

-

-

-

1,000

-

R-502c

zeotrope

R-22/115 (48.8/51.2)

A1

21

73,000

330

-

-

-

1,000

2-0-0b

R-503c

zeotrope

R-23/13 (40.1/59.9)

-

-

-

-

-

-

-

1,000

2-0-0b

R-504c

zeotrope

R-32/115 (48.2/51.8)

-

28

140,000

450

-

-

-

1,000

-

* * *

R-507A

zeotrope

R-125/143a (50.0/50.0)

A1

32

130,000

 510

-

-

-

1,000

2-0-0b

* * *

R-509A

zeotrope

R-22/218 (44.0/56.0)

A1

24

75,000

 380

-

-

-

1,000

2-0-0b

R-510A

zeotrope

R-E170/600a (88.0/12.0)

A3

0.87

7,300

14

3.5

29,000

56.1

1,000

-

R-511A

zeotrope

R-290/E170 (95.0/5.0)

A3

0.59

5,300

9.5

2.4

21,000

38

1,000

-

R-512A

azeotrope

R-134a/152a (5.0/95.0)

A2

1.9

11,000

31

7.7

45,000

123.9

1,000

-

* * *

R-516A

azeotrope

R-1234yf/134a/152a (77.5/8.5/14.0)

A2

 3.2

13,000

 52

13.1

50,000

210.1

590

-

R-600

CH3CH2CH2CH3

butane

A3

0.15

1,000

2.4

3.0

20,000

48

1,000

1-4-0

R-600A

CH(CH3)2CH3

2-methylpropane (isobutane)

A3

0.59

4,000

 9.5

2.4

16,000

38

1,000

2-4-0

R-601

CH2CH2CH2CH2CH3

pentane

A3

0.18

1,000

2.9

2.2

12,000

35

600

-

R-601A

(CH3)2CHCH2CH3

2-methylbutane (isopentane)

A3

0.18

1,000

2.9

2.4

13,000

38

600

-

* * *

R-744

CO2

carbon dioxide

A1

 3.4

 30,000

 54

-

-

-

5,000

2-0-0

R-1130 (E )

CHCI=CHCI

trans-1,2-dichloroethene

 B2

0.25

1,000

4.0

16

65,000

258

200

-

R-1132A

CF2=CH2

1,1-difluoroethene

A2

2.0

13,000

33

8.1

50,000

131

500

-

R-1150

CH2=CH2

ethene (ethylene)

 B3

-

-

-

2.2

31,000

36

200

1-4-2

* * *

R-1234yf

CF3CH=CH2

2,3,3,3-tetrafluoro-1-propene

 A2L

 4.5

16,000

75

18

62,000

289

500

-

R-1234ze(E)

CF3CH=CFH

trans-1,3,3,3-tetrafluoro-1 -propene

 A2L

4.7

16,000

76

18.8

65,000

303

800

-

* * *

R-1336mzz(Z)

CF3CHCHCF3

cis-1,1,1,4,4,4-hexaflouro-2-butene

A1

5.2

13000

 84

-

-

-

500

-

For SI: 1 pound = 0.454 kg, 1 cubic foot = 0.0283 m3.

a.                     Degrees of hazard are for health, fire, and reactivity, respectively, in accordance with NFPA 704.

b.                     Reduction to 1-0-0 is allowed if analysis satisfactory to the code official shows that the maximum concentration for a rupture or full loss of refrigerant charge would not exceed the IDLH, considering both the refrigerant quantity and room volume.

c.                     Class I ozone depleting substance; prohibited for new installations

d.                     Occupational Exposure Limit based on the OSHA PEL, ACGIH TLV-TWA, the TERA WEEL or consistent value on a time-weighed average (TWA) basis (unless noted C for ceiling) for an 8 hr/d and 40 hr/wk.

e.                     LFL is based on the Worst Case of Formulation for Flammability (WCF) @ 73.4°F (23°C) unless otherwise noted.

f.                     Worst Case of Fractionation for Flammability (WCFF) LFL @ 140°F (60°C).

g.                     WCFF LFL @ 73.4°F (23°C)

h.                     WCF LFL @ 212°F (100°C).

 

*                     *                     *

 

 

 

 

 

 

*                     *                     *

 

SECTION 1104 SYSTEM APPLICATION REQUIREMENTS

 

*                     *                     *

 

[Delete Section 1104.3.1 and replace as follows:]

 

M-1104.3.1 Air Conditioning for human comfort. High-probability systems used for human comfort shall use Group A1 and A2L refrigerant.

 

Exceptions:

 

1.                     Equipment listed for and used in residential occupancies containing a maximum of 6.6 pounds (3 kg) of refrigerant.

2.                     Equipment listed for and used in commercial occupancies containing a maximum of 22 pounds (10 kg) of refrigerant.

3.                     Industrial occupancies.

 

[Delete Section 1104.3.2 and replace as follows:]

M-1104.3.2 Group A2, A3, and B3 refrigerants. Group A2 and B2 refrigerants shall not be used in high probability systems. Group A3 and B3 shall not be used except where approved.

                     Exceptions: This section does not apply to:

1.                     Laboratories where the floor areas per occupant is not less than 100 square feet (9.3 m2).

2.                     Listed self-contained systems having a maximum of 0.331 pounds (150 G) of Group A3 refrigerant.

3.                     Industrial Occupancies.

4.                     Equipment listed for and used in residential occupancies containing a maximum of 6.6 pounds (3 kg) of Group A2 or B2 refrigerant.

5.                     Equipment listed for and used in commercial occupancies containing a maximum of 22 pounds (10 kg) of Group A2 or B2 refrigerant.

 

[Delete Table 1104.3.2 in its entirety, without substitution.]

 

*                     *                     *

 

SECTION 1106 MACHINERY ROOMS, GENERAL REQUIREMENTS

 

*                     *                     *

 

[Delete Section 1106.3 and replace as follows:]

M-1106.3 Class 2 and Class 3 refrigerants. Where refrigerants of Groups A2, A3 and B3 are used, the machinery room shall conform to the Class 1. Division 2, hazardous location classification requirements of NFPA 70.

*                     *                     *

 

[Delete Section 1106.4 in its entirety, including Table 1106.4.2, and replace as follows:]

M-1106.4 Group A2L and B2L Refrigerant. Machinery rooms for Group A2L and B2L refrigerant shall comply with Sections 1106.4. through Section 1106.4.3.

 

M-1106.4.1 Elevated Temperatures. Open flame-producing devices or continuously operating hot surfaces over 1290℉ (700°C) shall not be permanently installed in the room.

 

M-1106.4.2 Refrigerant detector. In addition to the requirements of Section 1105.3, refrigerant detectors shall signal an alarm and activate the ventilation system in accordance with the response time specified in Table 1106.4.2.

 

Table M-1106.4.2

Group A2L and B2l Detector Activation

Activation Level

Maximum Response Time (seconds)

ASHRAE 15 Ventilation Level

Alarm Reset

Alarm Type

Less than or equal to the OEL in Table 1103.1

300

1

Automatic

Trouble

Less than or equal to the refrigerant concentration level in Table 1103.1

15

2

Manual

Emergency

 

 

M-1106.4.3 Mechanical Ventilation. The machinery room shall have a mechanical ventilation system complying with ASHRAE 15.

 

*                     *                     *

SECTION 1107 PIPING MATERIAL

*                     *                     *

 

[Delete Table 1107.4 and replace as follows:]

TABLE M-1107.4 REFRIGERANT PIPE

PIPING MATERIAL

STANDARD

Aluminum tube

ASTM B210/ASTM B210M, ASTM B491M

Brass (copper alloy) pipe

ASTM B43

Copper linesets

ASTM B280, ASTM B1003

Copper pipe

ASTM B42, ASTM B302

Copper tubea

ASTM B68, ASTM B75, ASTM B88, ASTM B280, ASTM B819

Steel pipeb

ASTM A53, ASTM A106, ASTM A333

Steel tube

ASTM A254, ASTM A334

a.                     Soft annealed copper tubing larger than 1 3/8-inch (35 mm) O.D. shall not be used for field assembled refrigerant piping unless it is protected from mechanical damage.

b.                     ASTM A53, Type F steel pipe shall only permitted for discharge lines in pressure relief systems.

*                     *                     *

 

 

[Delate Table 1107.5 and replace as follows:]

 

TABLE M-1107.5 REFRIGERANT PIPE FITTINGS

FITTING MATERIAL

STANDARD

Aluminum

ASTM B361

Copper and Copper Alloy (Brass)

ASME B16.15, ASME B16.18, ASME B16.22, ASME B16.24, ASME B16.26, ASME B16.50

Steel

ASTM A105, ASTM  A181, ASTM A193, ASTM A234, ASTM A420, ASTM A707

 

 

*                     *                     *

 

[Delete Section 1107.7 and replace as follows:]

M-1107.7 Flexible connectors, expansion and vibration compensators. Flexible connectors and expansion and vibration control devices shall be listed and labeled for use in refrigerant systems and pressures for which the components are installed.

 

*                     *                     *

 

SECTION 1109 REFRIEGERANT PIPE INSTALLATION

 

*                     *                     *

 

[Delete Section 1109.2.2 and replace as follows:]

M-1109.2.2 Refrigerant and pipe enclosure. Refrigerant piping shall be protected by locating it within the building elements or within protective enclosures.

Exception: Piping protection within the building elements or protective enclosure shall not be required in any of the following locations:

1.                     Where installed without ready access or located more than 7 feet 3 inches (2210 mm) above the finished floor.

2.                     Where located within 6 feet (1829 mm) of the refrigerant unit or appliance.

3.                     Where located in a machinery room complying with Section 1105.

4.                     Outside the building:

1.1                     Protected from damage from the weather, including but not limited to, hail, ice, and snow loads and

1.2                     Protected from damage within the expected foot or traffic path or

1.3                     Outside, underground, installed not less than 8 inches (200 mm) below finished grade and protected against corrosion.

 

[Delete Section 1109.2.3 and replace as follows:]

M-1109.2.3 Prohibited Locations. Refrigerant piping shall not be installed in any of the following locations:

1.                     Exposed within a fire resistance-rated exit access corridor.

2.                     Exposed within an interior exit stairway.

3.                     Within an interior exit ramp

4.                     Within an exit passageway

5.                     Within an elevator, dumbwaiter or other shaft containing a moving object.

 

*                     *                     *

 

[Delete Section 1109.2.5 and replace as follows:]

M-1109.2.5 Refrigerant pipe shafts. Refrigerant piping that penetrates two or more floor/ceiling assemblies shall be enclosed in a fire resistance-rated shaft enclosure. The fire-resistance-rated shaft enclosure shall comply with Section 713 of the International Building Code.

Exceptions:

1. Refrigeration systems using R-718 refrigerant (water).

2. Piping in a direct refrigeration system where the refrigerant quantity does not exceed the limits of Table 1103.1 for the smallest occupied space through which the piping passes.

3. Piping located on the exterior of the building where vented to the outdoors.

 

*                     *                     *

 

[Delete Section 1109.2.6 and replace as follows:]

M-1109.2.6 Exposed piping surface temperature. Exposed piping with ready access to nonauthorized personnel having surface temperatures greater than 120℉ (69°C) or less than 5℉ (-15°) shall be protected from contact or shall have thermal insulation that limits the exposed insulation surface temperature to a range of 5℉ (-15°C) to 120℉ (69°C).

 

*                     *                     *

 

[Delete Section 1109.2.7 and replace as follows:]

M-1109.2.7 Pipe identification. Refrigeration pipe located in areas other than the room or space where the refrigerating equipment is located shall be identified. The pipe identification shall be located at intervals not exceeding 20 feet (6096 mm) on the refrigerant piping or pipe insulation. The minimum height of lettering of the identification label shall be ½ inch (12.7 mm). The identification shall indicate the refrigerant designation and safety group classification of refrigerant used in the piping system. For Group A2L and B2L refrigerants, the identification shall also include the following statement: “WARNING - Risk of Fire. Flammable Refrigerant.” For Group A2, A3, B2 and B3 refrigerants, the identification shall also include the following statement: “DANGER - Risk of Fire or Explosion. Flammable Refrigerant.” For any Group B refrigerant, the identification shall also include the following statement: “DANGER - Toxic Refrigerant.”

*                     *                     *

 

[Delete Section 1109.3 and replace as follows, but leave Table 10.9.3.2 unchanged:]

M-1109.3 Installation requirements for Group A2L, A2, A3, B2L, B2, or B3 refrigerant. Piping systems using Group A2L, A2, A3, B2L, B2, or B3 refrigerant shall comply with the requirements of Section 1109.3.1 and 1109.3.2.

 

M-1109.3.1 Pipe Protection. In addition to the requirements of Section 305.5, aluminum, copper, and steel tube used for Group A2, A3, B2L, B2, and B3 refrigerants and located in concealed locations where tubing is installed in studs, joists, rafters or similar member spaces, and located less than 1½ inches (38 mm) from the nearest edge of the member, shall be continuously protected by shield plates. Protective steel shield plates having a minimum thickness of 0.0575 inch (1.46 mm) (No. 16 gage) shall cover the area of the tube plus the areas extending not less than 2 inches (51 mm) beyond both sides of the tube. 

 

M-1109.3.2 Shaft ventilation. Refrigerant pipe shafts with systems using Group A2L or B2L refrigerant shall be naturally or mechanically ventilated. Refrigerant pipe shafts with one or more systems using any Group A2, A3, B2, or B3 refrigerant shall be continuously mechanically ventilated and shall include a refrigerant detector. The shaft ventilation exhaust outlet shall comply with Section 501.3.1. Naturally ventilated shafts shall have a pipe, duct or conduit not less than 4 inches (102 mm) in diameter that connects to the lowest point of the shaft and extends to the outdoors. The pipe, duct or conduit shall be level or pitched downward to the outdoors. Mechanically ventilated shafts shall have a minimum airflow velocity in accordance with Table 1109.3.2. The mechanical ventilation shall be continuously operated or activated by a refrigerator. Systems utilizing a refrigerant detector shall activate the mechanical ventilation at a maximum refrigerant concentration of 25 percent of the lower flammable limit of the refrigerant. The detector, or a sampling tube that draws air to the detector, shall be located in an area where refrigerant from a leak will concentrate. The shaft shall not be required to be ventilated for double-wall refrigerant pipe where the interstitial space of the double-wall pipe is vented to the outdoors.

 

*                     *                     *

 

[Delete Section 1109.4 in its entirety, without substitution]

 

 

*                     *                     *

 

[Delete Section 1109.7 in its entirety, without substitution]

 

*                     *                     *

 

SECTION 1110 REFRIGERATION PIPING SYSTEM TEST

 

*                     *                     *

 

[Delete Section 1110.3 and replace as follows:]

M-1110.3 Test gases. The medium used for pressure testing the refrigerant system shall be one of the following inert gases: oxygen-free nitrogen, helium, argon or premixed nonflammable oxygen-free nitrogen with a tracer of gas of hydrogen or helium. For R-744 refrigerant systems, carbon dioxide shall be allowed as the test medium, For R-718 refrigerant systems, water shall be allowed as the test medium.

M-1110.3.1 Test gases not permitted. Oxygen, air, refrigerants other than those identified in Section 1110.3, combustible gases and mixtures containing such gases shall not be used as the pressure test medium.

 

*                     *                     *

 

[Delete Section 1110.5 and replace as follows:]

M-1110.5 Piping system strength test. Refrigerating system components and refrigerant piping shall be tested in accordance with ASME B31.5 or this section. Separate tests for isolated portions of the system are permitted and provided that all required portions are tested at least once. Pressurize with test gas for a minimum of 10 minutes to not less than the lower of (a) the lowest design pressure for any system component, or (b) the lowest value of set pressure for any pressure relief devices in the system. The design pressures for determination of test pressure shall be the pressure identified on the label nameplate of the condensing unit, compressor, compressor unit, pressure vessel, or other system component with a nameplate. A passing test result shall have no rupture or structural failure of any system component or refrigerant piping. Refrigerant popping and tubing greater than ¾ inches in diameter shall be tested in accordance with ASHRAE 15.                                                                                                                              

 

[Delete Section 1110.6 in its entirety, without substitution]

 

[Delete Section 1110.7 in its entirety, without substitution]

 

*                     *                     *

 

CHAPTER 15

REFERENCED STANDARDS

 

*                     *                     *

 

[Add ASHRAE reference as follows:]

ASHRAE                                                                                                                                                                                             ASHRAE

1791 Tullie Circle NE

Atlanta, GA 30329

15-2022                                          Safety Standard for Refrigeration Systems

34-2022                                          Designation and Safety Classification of Refrigerants

 

*                     *                     *

 

[Add ASTM reference as follows:]

ASTM                                                                                                                                                                                             ASTM International

                                                                                                                                                   100 Bar Harbor Drive, P.O. Box C700                                                                                                                                                                                                                   West Conshohocken, PA

A333-18                     Standard Specification for Seamless and Welded Steel Pipe for Low-Temperature Service and other Applications with required Notch Toughness

 

*                     *                     *

 

[Add UL reference as follows:]

UL                                                                                                                                                   UL, LLC

                                                                                                                                                   333 Pfingsten Road,

                                                                                                                                                   Northbrook, IL 60062-2096

UL/CSA 60335-2-40                      2022                     Household and Similar Electrical Appliances-Safety-                                                               Part 2-40: Particular Requirements for Electrical Heat                                                                Pumps, Air Conditioners and Dehumidifiers

UL/CSA 60335-2-89  2021                     Household and Similar Electrical Appliances-Safety-                                                               Part2-89: Particular Requirements for Commercial                                                                Refrigerating Appliances with an Incorporated or Remote                                                                Refrigerant Unit or Compressor.

 

*                     *                     *

End